Back to test & tag Print or save this page for your audit folder
Quick reference · AS/NZS 3760:2022

Test & tag retest intervals

For aged care, supported accommodation and NDIS equipment
Ampcare
0404 066 247
ampcare.com.au

The standard does not set intervals by room name. Table 2.4 keys them to how an item is used — whether its cord is flexed in normal use, whether it is open to abuse, and whether it sits in a hostile environment. A hoist wheeled between rooms and a desktop PC that never moves sit at opposite ends of the same table.

Equipment intervals
Usage class Interval Typical items on your site
Cord flexed, open to abuse, or hostile environment 12 months Hoists, electric beds, power chairs, scooters, chargers, vacuums, kitchen appliances, extension leads, power boards
Commercial cleaning equipment 6 months Floor polishers, carpet extractors, industrial vacuums
Construction, demolition & workshop use 3 months Portable power tools, site leads, portable RCDs
Hire & loan equipment Before each hire Loan chairs, shower commodes, mobile hoists moving between users
Residential-type settings, static items 2 years Fixed appliances in supported accommodation and boarding-house-style settings
Not flexed, not open to abuse, not hostile Up to 5 years Desktop PCs, monitors, printers and similar that never move in use
RCD (safety switch) intervals
Device Push-button Trip-time test
Fixed RCD at the board 6 months 12 months — or 2 years for static, low-risk residential settings
Portable RCD 3 months 12 months
NOTE
Push-button checks are a task for your own staff between visits. Trip-time testing needs a calibrated instrument and is what Ampcare performs. A site risk assessment may set shorter intervals than these — that is always acceptable. Testing less often than the standard is not.
Ampcare — mobile test & tag and AT servicing, Brisbane
$85 call-out covering your first 10 items · $4.50 per item under 30 · $3.00 per item for 30+ in aged care and supported accommodation · RCD trip-time testing included · every result published to your own asset portal at no cost.
Brisbane · Logan · Ipswich · Redlands (mainland) · Moreton Bay  |  ABN 12 971 043 598  |  Restricted Electrical Work Licence, to 250VAC
Get a quote
0404 066 247
Prepared as a plain-language summary of AS/NZS 3760:2022 Table 2.4 for planning purposes. It is not a substitute for the standard itself, and the class applying to any given item is assessed on site.